PHHS SERIES

PHHS-56DS12K15

Horizontal split water-to-air — standard

Original Polar Bear water-to-air equipment photographPolar Bear equipment photograph
SPECIFICATIONS

Ratings

Capacity in Btu/h at the entering water temperature (EWT) shown. This two-step model is listed at part load and full load.

StageHeating 50°FHeating 32°FCooling 50°FCooling 70°FCOP 50°F / 32°FSEER 50°F / 70°F
Part load37,00034,00040,00037,0004.4 / 3.917.9 / 17.1
Full load56,00050,00060,00056,0004.3 / 3.817.6 / 16.7
Compressor nominal51,000 Btu/h
Compressor cabinet W × D × H36 × 36 × 28 in
Air handler cabinet L × D × H42 × 32 × 28 in

Ratings as published in the Polar Bear product specification, in Btu/h at the entering water temperature (EWT) shown; cooling efficiency is listed as published (SEER). Selection at your design conditions is confirmed with the factory.

See the full PHHS spec chart ↗

Electrical

“D” in the model number means 230 V single-phase power. Every model is also available in the voltages offered for its compressor, with ECM fan motors or three-phase motors with inverters. Confirm voltage, clearances and accessories when ordering.