PBWW SERIES
PBWW-42DS12
Water-to-water
Polar Bear equipment photographSPECIFICATIONS
Ratings
Capacity in Btu/h at the entering water temperature (EWT) shown.
| Stage | Heating 50°F | Heating 32°F | Cooling 50°F | Cooling 70°F | COP 50°F / 32°F | SEER 50°F / 70°F |
|---|---|---|---|---|---|---|
| Single stage | 42,000 | 36,500 | 40,000 | 36,000 | 4.4 / 3.9 | 17.6 / 16.7 |
Compressor nominal42,000 Btu/h
Cabinet W × D × HFamily options: 48 × 42 × 31.5 or 36 × 36 × 26 in; exact model mapping pending
Ratings as published in the Polar Bear product specification, in Btu/h at the entering water temperature (EWT) shown; cooling efficiency is listed as published (SEER). Selection at your design conditions is confirmed with the factory.
See the full PBWW spec chart ↗
Electrical
“D” in the model number means 230 V single-phase power. Every model is also available in the voltages offered for its compressor, with ECM fan motors or three-phase motors with inverters. Confirm voltage, clearances and accessories when ordering.