PBWW SERIES
PBWW-30S12K10
Water-to-water
Polar Bear equipment photographSPECIFICATIONS
Ratings
Capacity in Btu/h at the entering water temperature (EWT) shown. This two-step model is listed at part load and full load.
| Stage | Heating 50°F | Heating 32°F | Cooling 50°F | Cooling 70°F | COP 50°F / 32°F | SEER 50°F / 70°F |
|---|---|---|---|---|---|---|
| Part load | 19,800 | 17,400 | 18,500 | 16,500 | 4.4 / 3.9 | 17.6 / 16.7 |
| Full load | 30,000 | 26,400 | 28,000 | 25,000 | 4.3 / 3.8 | 17.4 / 16.5 |
Compressor nominal30,000 Btu/h
Cabinet W × D × HFamily options: 48 × 42 × 31.5 or 36 × 36 × 26 in; exact model mapping pending
Ratings as published in the Polar Bear product specification, in Btu/h at the entering water temperature (EWT) shown; cooling efficiency is listed as published (SEER). Selection at your design conditions is confirmed with the factory.
See the full PBWW spec chart ↗
Electrical
Every model is available in the voltages offered for its compressor, with ECM fan motors or three-phase motors with inverters. Confirm voltage, clearances and accessories when ordering.